Questions & Answers › Before we start on site
Can you explain why instantaneous gas is viable, but electric is not? Given than gas will still face the same issues with the colder Canberra waters
What the law says
The Residential Zones Policy (Territory Plan 2023, NI2023-540, Part E01), assessment requirement 10, says no new gas network connections are allowed to all new or existing developments, including redevelopments.
The Subdivision Policy (NI2023-540, Part F01), requirement 13, says no gas mains connections are to be provided to new residential blocks.
This matters when you compare gas and electric. A gas unit is only an option if gas can be supplied to the building under these rules. Please ask us about your block before assuming gas is available.
Why electric instantaneous struggles in Canberra, and gas does not on energy grounds
Gas faces the same cold incoming water as electric. Either type has to supply the same amount of energy. The difference is where that energy comes from. Electric is limited by how much power we can safely draw and the limits placed on residential supply. Gas is not limited in the same way.
We set the performance standard for a typical household. We need to anticipate two showers running at the same time.
Typical water-saving showerheads use 9L per minute. So two showers will use 18L per minute, or 1,080 litres per hour. For a comfortable hot shower, the recommended temperature is 38°C to 40°C. According to the reservoir reports, the cold temperature is 7.5°C, so we need to heat the water by at least 30.5°C.
The energy required to heat water is determined by the specific heat capacity of water, which is 4.186 J/g°C. This means it requires 4.186 J of energy to heat a gram of water by one degree. So we need to heat 1,080L of water by 30.5 degrees. This means we need 138,000,000 joules every hour, or 138MJ/hr. To supply this amount of energy, assuming 95% efficiency, we will need an electric system of 40.3kW.
This is a very large amount of power for residential use. The maximum size for most residential units, even with three-phase, is 27kW. In the spec sheets of a three-phase heating unit, the 18kW unit is barely able to provide enough hot water for one shower, and the 27kW unit is not enough for two showers at the same time in cold weather. Two showers at once would need two three-phase heating units.
Electric instantaneous is not impossible. To handle Canberra's cold water, we would need significant electrical upgrades to the existing consumer mains and power service cables, and a dedicated circuit wired directly to the hot water service. This is a large upfront investment, anywhere from $4,000 to $14,000 depending on the existing infrastructure. For this reason we do not recommend it as the main system.
Gas, while less efficient, does not have this limit as it is a very energy-dense product. Each kg of gas provides 20MJ of energy. Most gas systems are rated for 20+ litres per minute for a 30 degree rise. On energy alone, gas copes with Canberra's cold water. Whether gas can be supplied to your new building is a separate question, and the planning rules above apply.
CGFB-Q-0637 · last reviewed 24 November 2026
Related questions
- How are new connections made to a new building from an existing building? These connections include sewer, electricity, gas, water, storm water
- If a residence has two separate utility meters, can a Secondary Residence have a third meter?
- At what stage during the build will the power, water, gas and sewer facilities be functional?
- What is the process if we need to get our power lines that connects energy to our house moved because of the proposed development?