How close can a Secondary Residence be to the existing house before requiring a fire rated wall?
What the law says
Fire separation is a National Construction Code (NCC) matter. It is assessed for Building Approval under the Building Act 2004 (A2004-11). The planning rules in the Planning (Residential Zones) Technical Specifications 2026 (NI2026-303) do not set this distance.
Fire-resisting construction is generally needed where a Class 1 building, such as a Secondary Residence, is less than 1.8m from another building on the same block, such as the existing house. Some exceptions apply.
Only the part of the wall that is closer than 1.8m needs to be fire rated, not the whole wall. For example, if one corner is 1.6m from the existing house, only the part of the wall closer than 1.8m needs to be fire rated.
Where a wall must be fire rated, the NCC allows walls achieving a fire resistance level (FRL) of at least 60/60/60, or specified masonry construction.
The 1.8m distance applies between two Class 1 buildings. A separate rule applies to a wall less than 900mm from a property boundary. That wall also needs to be fire rated.
If the Secondary Residence is attached to the existing house, extra requirements for the separating wall may apply.
How we do it
We mark the fire-rated wall on your plans with an arrow and the label 'fire rated wall'. A fire-rated wall is an additional cost.
Your building certifier confirms the exact requirement for your design, based on the version of the NCC used for your Building Approval.